THE INVESTIGATION OF DISTRIBUTION OF THE MAGNETIC FLUX DENSITY OF OPERATING TWO-CIRCUIT POWER LINE 110 KV «CHTPP-CHERNIHIV-330» IN THE RESIDENTIAL AREA AND METHODS OF ITS DECREASING TO A SAFE LEVEL
DOI:
https://doi.org/10.20998/2074-272X.2020.6.08Keywords:
overhead transmission line, electric loads, magnetic flux density, residential buildingAbstract
Purpose. The problem of evaluation and analysis of magnetic flux density of overhead power lines is very relevant now, since the magnetic field of industrial frequency can have a negative effect on human health. The analysis of the magnetic field of the operating double-circuit overhead transmission line was made in this work. This overhead line is in the residential area of Chernihiv, Ukraine. The purpose of this work is to determine safe habitation conditions as a function of the magnetic flux density along the route of two-circuit power line with the voltage 110 kV «ChTPP-Chernihiv-330». Real modes of operation are taken into account. Recommendations are given for reducing the magnetic flux density level in the residential area to a value that will not exceed the standard value. Methodology. Methods of electromagnetic field theory were used to calculate the magnetic field of power lines. The location of the phase wires on different types of supports of the existing power transmission line and the minimum distance between the conductors and the ground were taken into account. The current value of the current in the phases of the transmission line was taken from the Company «Chernihivoblenergo». Also, the calculation of the magnetic flux density was made for the perspective loads of the transmission line. Estimation of the value of the magnetic flux density was made for the zone of one-story and multi-story buildings near power lines. The option of uniform loading of two power transmission lines was considered and the case where the entire load is transferred along one circuit was also considered. Results. In this work, the distribution of magnetic flux density at a height of 1.8 m in the direction perpendicular to the power transmission line for the sections built on supports of the U110-2 and PB110-2 types was obtained. The graphs show that the magnitude of the magnetic flux density at the boundary of the protection zone of the transmission line will be exceed twice the standard value 0.5 μT for the existing and perspective loads. This problem is relevant in the case of transmission lines in single-circuit mode. The graphs of distribution of magnetic flux density on the facade of an apartment building, located at a distance of 20 m from the axis of symmetry of the transmission line, were constructed. As a result, it is shown that at a height of 11 m from the earth's surface, magnetic flux density will be 1.5-2 μT. Practical value. It is determined that safe habitation along the route of two-circuit power line with the voltage 110 kV «ChTPP-Chernihiv-330» can be achieved when facades of an apartment building are removed from the axis of symmetry of the transmission line at a distance of 33 m for high-rise buildings and at a distance of 27 m for one-storey buildings. Recommendations for reducing the magnetic flux density of this power transmission line have been developed.
References
Marincu A., Greconici M., Musuroi S. The electromagnetic field around a high voltage 400 kV electrical overhead lines and the influence on the biological systems. Facta universitatis - series: Electronics and Energetics, 2005, vol. 18, no. 1, pp. 105-111. doi: 10.2298/fuee0501105m.
Conti R., Giorgi A., Rendina R., Sartore L., Sena E.A. Technical Solutions To Reduce 50 Hz Magnetic Fields from Power Lines. Proceedings of Power Tech Conference IEEE 2003, 23-26 June, 2003, Bologna (Italy), 2003, vol. 2, 6 p. doi: 10.1109/ptc.2003.1304685.
Moro F., Turri R. Fast analytical computation of power-line magnetic fields by complex vector method. IEEE Transactions on Power Delivery, 2008, vol. 23, no. 2, рр. 1042-1048. doi: 10.1109/tpwrd.2007.915212.
Electrical installation regulations. Kharkiv,FortPubl., 2017. 760 p. (Ukr).
Krasnozhon A.V., Buinyi R.O., Pentegov I.V. Calculation of active power losses in the grounding wire of overhead power lines. Technical electrodynamics, 2016, no. 4, pp. 23-25. (Ukr). doi: 10.15407/techned2016.04.023.
Geri A., Locatelli A., Veca G.M. Magnetic fields generated by power lines. IEEE Transactions on Magnetics, 1995, vol. 31, no. 3, pp. 1508-1511. doi: 10.1109/20.376316.
Moro F., Turri R. Accurate calculation of the right-of-way width for power line magnetic field impact assessment. Progress In Electromagnetics Research B, 2012, vol. 37, рр. 343-364. doi: 10.2528/pierb11112206.
Pelevin D.Ye. The methods of reducing of the magnetic fields of overhead power lines outside security zones. Technical Electrodynamics, 2014, no. 5, pp. 14-16. (Rus).
Rozov V.Yu., Reutskyi S.Yu., Pelevin D.Ye., Yakovenko V.N. The research of magnetic field of high-voltage AC transmissions lines. Technical Electrodynamics, 2012, no. 1, pp. 3-9. (Rus).
Rozov V.Yu., Reutskyi S.Yu., Pelevin D.Ye., Pyliugina O.Yu. The magnetic field of power transmission lines and the methods of its mitigation to a safe level. Technical Electrodynamics, 2013, no. 2, pp. 3-9. (Rus).
Shangzun Y., Pengfei L., Ling N. Study on electromagnetic radiation of ultra-high voltage power transmission line. International Conference on Computer Science and Information Technology, 2008, pp. 402-406. doi: 10.1109/ICCSIT.2008.92.
SOU-N ЕЕ 20.179:2008. Calculation of electric and magnetic fields of power lines. Method (with changes). Kyiv, Minenergovugillja Ukrainy Publ., 2016. 37 p. (Ukr).
Rozov V.Yu., Reutskiy S.Yu., Piliugina O.Yu. The method of calculation of the magnetic field of three-phase power lines. Technical electrodynamics, 2014, no. 5, pp. 11-13. (Rus).
Scheme of perspective development of 35-110 kV electric grids on PJSC «Chernihivoblenergo» for 2017-2027. Kyiv, PJSC PTI «Kyivorgbud», 2017. (Ukr).
Regulating Power Line EMF Exposure: International Precedents. Available at: https://elc.uvic.ca/wordpress/wp-content/uploads/2015/01/Regulating-Power-Line-EMF-Exposure.pdf (Accessed 02 August 2020).
Burnett J., Yaping P.D. Mitigation of extremely low frequency magnetic fields from electrical installations in high-rise buildings. Building and Environment, 2002, vol. 37, no. 8-9, pp. 769-775. doi: 10.1016/S0360-1323(02)00043-4.
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2020 A. V. Krasnozhon, R. O. Buinyi, I. V. Dihtyaruk, A. O. Kvytsynskyi
This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.
Authors who publish with this journal agree to the following terms:
1. Authors retain copyright and grant the journal right of first publication with the work simultaneously licensed under a Creative Commons Attribution License that allows others to share the work with an acknowledgement of the work's authorship and initial publication in this journal.
2. Authors are able to enter into separate, additional contractual arrangements for the non-exclusive distribution of the journal's published version of the work (e.g., post it to an institutional repository or publish it in a book), with an acknowledgement of its initial publication in this journal.
3. Authors are permitted and encouraged to post their work online (e.g., in institutional repositories or on their website) prior to and during the submission process, as it can lead to productive exchanges, as well as earlier and greater citation of published work.