GUARANTEEING THE TROUBLE-FREE OPERATION OF CAPACITOR BANKS IN POWER-SUPPLY SYSTEMS OF INDUSTRIAL ENTERPRISES
DOI:
https://doi.org/10.20998/2074-272X.2016.1.10Keywords:
power supply system, resonance, capacitor bank, power quality, electromagnetic compatibilityAbstract
Purpose. The problem of resonance phenomena in power systems of industrial enterprises using capacitor banks for reactive power compensation was detected. Circuit of the capacitor banks tier to downshift main substation tires is present. But there is no common algorithm to calculate and avoid such trouble. The main goal of this article is to introduce some basics for power supply systems with possible resonant circuits engineering. Methodology. At the first step the data on the change of the current in the chemical company network when changing capacitor banks value are received. For these purposes the oscilloscope function of digital protection relay was used. Current data samples were analyzed by spectrum detection software. Most significant levels of the 3rd and 5th harmonics were achieved. Comparison of harmonic distortion levels with and without capacitor bank is given. Results. Achieved data allow making conclusion about overloading reasons of capacitor banks while higher harmonics currents presence. A voltage and current harmonious composition measuring in the absence of power quality analyzers using digital protection relay terminals or emergencies registers are proposed. The necessity of power quality monitoring near capacitor banks connections to avoid resonance phenomena (current and voltage resonance) in industrial power supply systems is proven. The control algorithm of capacitor banks to provide electromagnetic compatibility, while various modes of nonlinear load operation is given. Originality. Using of digital protection relay oscilloscoping for current resonant detection can allow to significally reduce time and cost of solution. Replacement parallel circuit comprising a branch and one active-inductive load to another branch network in the presence of higher harmonics source are proposed. Practical value. A sequence for measuring the levels of harmonic components at the connections of capacitor banks in the absence of specialized instruments is proposed. The algorithm to avoid possible resonance currents in the presence of condensing units is proposed.References
Gapon D.A., Bederak Ya.S. Features of the operation regime of the mains during soft start of powerful synchronous motors. Promyshlennaia energetika – Industrial Power Engineering, 2014, no.2, pp.27-30 (Rus).
Beliy V.B. Electromagnetic compatibility of power-supply systems’ elements comprising reactive power compensation devices. Vestnik Altaiskogo Gosudarstvennogo Agrarnogo Universiteta – Bulletin of the Altai State Agrarian University, 2009, no.6, pp. 62-65 (Rus).
Bederak Y.S., Oleynik S.V., Shuliak A.A. Research of capacitors mode 6 (10) kV connected to branches of dual limiting current reactor. Elektromekhanichni i enerhozberihaiuchi systemy – Electromechanical and energy saving systems, 2013, vol.2, part 2, pp. 290-294. (Ukr).
Bederak Y.S. Electromagnetic compatibility of complex industrial power supply systems Visnyk NTU «KhPІ» – Bulletin of NTU «KhPІ», 2014, no.60, pp. 37-45. (Ukr).
Shklyarskiy Ya.E., Skamin A.N. Industrial research into high harmonic influence on compensation devices. Elektrotekhnika i elektromekhanika – Electrical engineering & electromechanics, 2013, no.1, pp. 69-71 (Rus).
Rules of technical operation of electrical consumers, approved by the Ministry of Fuel and Energy of Ukraine 25.07.2006, no.258 (as amended by Order of the Ministry of Energy and Coal Industry of 13.02.2012 no.91) with amendments, approved by the Ministry of Energy and Coal Industry of Ukraine 11.16.2012 no.905. (Ukr).
State Standard 13109-97. Electric Energy. Compatibility of technical equipment. Standards of quality of electric energy in power systems for general use. Interstate standard. Moscow, IPC Standards Publ., 1998. 31 p. (Rus).
IEEE Standard 519-1992. IEEE recommended practices and requirements for harmonic control in electrical power systems. – 100 p.
Bederak Y.S. Current and voltage monitoring implementation with varying load character in the branches of twin reactor in the presence of higher harmonics sources. Enerhetyka ta elektryfikatsiia – Energetic and electrification, 2013, no.8, pp. 48-51 (Ukr).
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2016 D. A. Gapon, Ya. S. Bederak
This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.
Authors who publish with this journal agree to the following terms:
1. Authors retain copyright and grant the journal right of first publication with the work simultaneously licensed under a Creative Commons Attribution License that allows others to share the work with an acknowledgement of the work's authorship and initial publication in this journal.
2. Authors are able to enter into separate, additional contractual arrangements for the non-exclusive distribution of the journal's published version of the work (e.g., post it to an institutional repository or publish it in a book), with an acknowledgement of its initial publication in this journal.
3. Authors are permitted and encouraged to post their work online (e.g., in institutional repositories or on their website) prior to and during the submission process, as it can lead to productive exchanges, as well as earlier and greater citation of published work.