SENSITIVITY ENHANCEMENT OF A HIGH-VOLTAGE POWER CABLES PARTIAL-DISCHARGE-CHARACTERISTICS-BASED DIAGNOSTICS SYSTEM BY MEANS OF LOW-PASS FILTERS

Authors

  • G. V. Bezprozvannych National Technical University "Kharkiv Polytechnic Institute", Ukraine
  • S. Laktionov National Technical University "Kharkiv Polytechnic Institute", Ukraine

DOI:

https://doi.org/10.20998/2074-272X.2012.6.08

Keywords:

controlled reactor, partial discharges, power cable with the cross-linked insulation, high-voltage low-pass filter, signal spectrum

Abstract

Modern high-voltage systems of capacitive objects diagnostics through partial discharge characteristics are sophisticated complexes containing oil-filled equipment. For them, partial discharges (PD) with apparent amplitude of 1000 pC are considered quite admissible. A controlled conventional-configuration reactor with 110 kV-class insulation cannot be directly connected to a tested power cable with cross-linked insulation and rated PD level not exceeding 2 pC. Suppression of probable pulse noise is carried out by means of a high-voltage low-pass filter application. In the article, results of a high-voltage filter frequency characteristics calculation in the frequency range of the PD signal spectrum are presented.

References

Gurin A.G., Besprozvannyh A.V., Naboka G.B., Naboka B.G. Vozbuzhdenie rezonansnyh kolebanij v buhtah kabelej dlya ocenki sostoyaniya izolyacii // Sbornik nauchnyh trudov HGPU "Informacionnye tehnologii: nauka, tehnika, tehnologiya, obrazovanie, zdorov'e". - Har'kov: HGPU. - 2001.

Naboka B.G., Nechaus A.A., Laktionov S.V. Ocenka urovnya chastichnyh razryadov v sisteme emkostej trehfaznogo transformatora // Vіsnik NTU "HPІ". - 2003. - № 9. - T.2. - S. 124-129.

Rezonansnij pristrіj kontrolyu chastkovih rozryadіv. Deklaracіjnij patent Ukraїni № u 2007 11370 vіd 15.10.2007 / Naboka B.G., Gurin A.G., Kononov B.T., Nechaus A.A., Laktionov S.V.

Naboka B.G., Gurin A.G., Laktionov S.V., Zolotarev V.M., Nechaus A.A. Obosnovanie dopustimyh rezhimov `ekspluatacii rezonansnyh ustanovok dlya diagnostiki kabelej.// Vіsnik NTU "HPІ". - 2005. - № 42. - S. 86-93.

Vdoviko V.P. Chastichnye razryady v diagnostirovanii vysokovol'tnogo oborudovaniya. - Novosibirsk, "Nauka". - 2008. - 150 s.

Ob`em i normy ispytanij `elektrooborudovaniya / Pod obsch. red. B.A. Alekseeva, F.L. Kogana, L.G. Mamikonyanca. − 6-e izd., s izm. i dop. − M.: Izd-vo NC `ENAS, 2004.

Meschanov G.I., Kabeli na napryazhenie 10-500 kV: sostoyanie i perspektivy razvitiya (analiz, prognoz, issledovaniya) / Shuvalov M.Yu., Kamenskij M.K., Obrazcov Yu.V., Ovsienko V.L. // Kabeli i provoda. − № 5 (312). − 2008.

Silovye kabeli srednego i vysokogo napryazheniya s izolyaciej iz sshitogo poli`etilena / Katalog. Zakrytoe akcionernoe obschestvo "Zavod Yuzhkabel'". 9. Red `E. Spravochnoe posobie po vysokochastotnoj shemotehnike. - M.: Mir, 1990. - 256 c.