INVESTIGATION OF EXPLOSION SAFETY OF DC POLYMER SURGE ARRESTERS 3.3 KV FOR TRACTION NETWORK OF RAILWAY TRANSPORT

Authors

  • Yu. N. Shumilov PSC «Slavyansk High Voltage Insulators Works», Ukraine
  • V. I. Bondarenko Donbass State Pedagogical University, Ukraine

DOI:

https://doi.org/10.20998/2074-272X.2019.2.10

Keywords:

electrical equipment of traction network, direct current, overvoltage protection, surge arrester, explosion safety, test procedure, explosive destruction, fragment separation

Abstract

In the testing laboratories of Ukraine, there is no high-voltage equipment of the necessary energy for testing surge arresters for explosion safety, which does not allow to estimate this indicator at the stage of development of prototypes. In view of this test, the polymer prototypes of the DC surge arresters in polymer case (SAp) 3.3 kV were tested under the operating conditions of the equipment of the operating substation with short-circuit currents of 8.3 kA and a current time of 0.02 seconds, close to the recommended by Standard of IEC 60099-4:2014 values. 8 samples of surge arresters were tested. A sample of the surge arrester was mounted on one of the metal supports at a height of 5.5 m located in the substation and connected to the 3.3 kV traction substation buses through disconnectors and a high-speed switch. After the short-circuit breaker was closed through a column with a pre-punched or shunted copper wire varistor, a short-circuit current flowed to form an electric arc inside the arrester samples. During the tests video samples were recorded using a video recorder installed in close proximity to the test sample. The frame of the SAp samples in which the varistors were enclosed was performed either by winding the fiberglass tape on a varistor column, or from rods arranged in the form of a squirrel cage, or in the form of a fiberglass tube with a hole for gas ejection during a short circuit inside the SAp. The destruction of the hull occurred without scattering of the fragments in seven cases from the eight samples tested. In seven samples, a local rupture of the silicone shell occurred in the varistor zone, a gas ejection and an arc discharge occurred through this gap. The exception was sample No. 2, made by a continuous winding of a glass-banding tape on a varistor column, in which, during the explosion, the upper electrode exploded with the simultaneous expansion of fragments of the varistor in a radius of 3-5 m. Due to the white smoke accompanying the explosion, it was not possible to fix on the frame whether the arc output from the case to the outside, despite the fact that on the next frame (in 33 ms.) the arc was no longer fixed. In the tests of eight of the presented designs, none of them ignited the hull. If the tests were carried out on the surge arresters assembled with pre-punched varistors (electrothermal breakdown), the varistors during the tests split, remaining inside the frame. From the action of the arc in the contact zone of the aluminum electrodes with varistors, a deep burn-out of the electrodes was observed, in some cases, the burnup was up to 7 mm deep and up to 8 mm wide. If the varistors were shunted by a copper wire, they remained intact. If the varistors were shunted by a copper wire, they remained intact und melting and burning out a part of the aluminum electrodes in the area of connection with the copper wire were smaller sizes. The samples showed a completely satisfactory ability to withstand large pulse currents without dispersing dangerous fragments for personnel and surrounding equipment. However, polymer designs, the frame of which is made by continuous winding, require reinforcement of the connection zone of the carcass with electrodes to exclude the break-out of electrodes during the accumulation of gases during a short circuit inside the shell of the SAp. For such designs, an additional test for mechanical strength in the longitudinal direction with a predetermined norm is required in the acceptance test program

References

Radchenko V.D. Tekhnika vysokikh napriazhenii ustroistv elektricheskoi tiagi [High voltage technique for electric traction devices].Moscow, Transport Publ., 1975. 359 p. (Rus).

Grubar L.O, Pertsovskiy L.M, Trofimov V.I. Ustroistvo, montazh i ekspluatatsiia tiagovykh podstantsii [Design, installation and operation of traction substations].Moscow, Transport Publ., 1971. 359 p. (Rus).

Radchenko V.D, Farafonov A.V. Vysokovol'tnye apparaty zashchity postoiannogo toka [DC high voltage protection devices].Moscow, Transport Publ., 1971. 142 p. (Rus).

IEC 60099-4. Ed.3.0 b: 2014. Surge arresters – part 4: Metal-oxide surge arresters without gaps a.c. systems. 2014. 168 p.

GOST R 55167-2012. Ogranichiteli perenapryajeniy nelineynyie dlya tyagovoy seti zheleznyh dorog. Obschie tehnicheskie usloviya. [GOST R 55167-2012. Surge arresters for power supply systems of electrified railways. General specifications].Moscow, Standartinform Publ., 2013. 15 p. (Rus).

GOST 12.2.007.0-75. Sistema standartov bezopasnosti truda. Izdeliya ehlektrotekhnicheskie. Obshchie trebovaniya bezopasnosti [GOST 12.2.007.0-75. Occupation safety standards system. Electrical equipment. General safety requirements].Moscow, Standartinform Publ., 2008. 10 p. (Rus).

Golubev P., Dmitriev V., Dmitriev M. Questions of the choice of the current explosion hazard of surge arresters 6-750 kV. Electrical engineering news, 2009, no.4(58). Available at: http://www.news.elteh.ru/arh/2009/58/13.php (Accessed 22 September 2017). (Rus).

Kapustin D. Pressure relief device in surge arrester. Test statistics. Electrical engineering news, 2004, no.1(25). Available at: http://www.news.elteh.ru/arh/2004/25/06.php (Accessed 08 May 2017). (Rus).

Bernhard A., Shmidt W. Surge arrester configuration with direct on moulded silicone insulation. Proceedings of World conference and exhibition on insulators, arresters and bushings: optimizing reliability, availability and cost through optimal selection of these components.Spain, 2003, pp. 97-106.

Hinrichen V. Latest designs and service experience with station-class polymer housed surge arresters. Proceedings of World conference and exhibition on insulators, arresters and bushings: optimizing reliability, availability and cost through optimal selection of these components.Spain, 2003, pp. 85-96.

Steinfeld K. Design of metal-oxide surge arresters. Proceedings of World conference and Exhibition on insulators, arresters and bushings: optimizing reliability, availability and cost through optimal selection of these components.Spain, 2003. pp. 137-146.

Published

2019-04-16

How to Cite

Shumilov, Y. N., & Bondarenko, V. I. (2019). INVESTIGATION OF EXPLOSION SAFETY OF DC POLYMER SURGE ARRESTERS 3.3 KV FOR TRACTION NETWORK OF RAILWAY TRANSPORT. Electrical Engineering & Electromechanics, (2), 66–70. https://doi.org/10.20998/2074-272X.2019.2.10

Issue

Section

Electrical Safety