INFLUENCE OF CORONARY DISCHARGE PARAMETERS ON THE EFFICIENCY OF LIGHTNING PROTECTION SYSTEM ELEMENTS

Authors

  • A. Yu. Chernukhin National Technical University «Kharkiv Polytechnic Institute», Ukraine

DOI:

https://doi.org/10.20998/2074-272X.2017.3.07

Keywords:

rod lightning terminal, pulse corona, electric field intensity of thunderstorm cloud, corona current, streamer speed

Abstract

Purpose. Investigation of the formation of space charge in the region of the apex of lighting rod, under the action of the electric field of a thunderstorm cloud, to evaluate the efficiency of elements of lighting protection systems. Methodology. We have applied the mathematical simulation of electromagnetic field distribution on the top of metal rod by different forms. As a mathematical apparatus, we use the finite element method. We considered two forms of the rod section: round and square. The round (cylindrical) rod has a sharp apex. The square rod has a flat top. The experimental study investigates the features of corona discharge formation. A high-voltage test equipment is created an electric field. Experiments carried out using a configuration consisting a potential plate and vertical rod electrode on grounded plate. The electric field strength varied from 1 kVm-1 to 100 kVm-1. This range corresponds to the thunderstorm condition. Results. We have obtained a correlation between the corona current and the strength of the electric field for various shapes of the rod top. The results of experimental studies confirmed the correctness of the conclusions of theoretical estimates. We show that the time parameters of streamer current pulses vary by no more than 30%, but a streamer charge increase to three time with increasing electric field strength. We proposed and applied a method for measuring the velocity of motion of a streamer in the discharge gap. As a result, it is established that the streamer speed is nonlinear in time. For a discharge gap of 1.2 m, the speed varies from 1.8∙104 m/s to 1.1∙106 m/s. Originality. For the first time, we have carried out a complex of studies of corona discharge parameters from lightning protector rod to apply for the certification procedure of ESE terminals. Practical value. Based on the set of obtained results, it is obviously that the standard NF C 17-102:2011 will not be introduced as a national standard of Ukraine before full introduction of scientifically justified data will be include into the requirements of the standard.

Author Biography

A. Yu. Chernukhin, National Technical University «Kharkiv Polytechnic Institute»

к.т.н., доцент каф. электрических аппаратов

References

1. NF C 17-102:2011 (Ed.2) Protection contre la foudre – Systèmes de protection contre la foudre à dispositif d’amorçage. Union Technique de l'Electricité (UTE), 2011. 82 p.

2. Kniazev V.V., Lesnoi I.P., Chernukhin A.Iu. Investigation results of the ESE-terminal and dissipaters’ parameters. Bulletin of NTU «KhPІ», 2008, no.21, pp. 78-87. (Rus).

3. Ortéga P., Heilbronner F., Rühling F., Díaz R., Rodière M. Charge–voltage relationship of the first impulse corona in long air gaps. Journal of Physics D: Applied Physics, 2005, vol.38, no.13, pp. 2215-2226. doi: 10.1088/0022-3727/38/13/021.

4. Moore C.B., Rison W., Mathis J., Aulich G. Lightning rod improvement studies. Journal of Applied Meteorology, 2000, vol.39, no.5, pp. 593-609. doi: 10.1175/1520-0450-39.5.593.

5. Bazelian E.M. The effect of the space charge of the corona in lightning protection. Trudy IV Rossiiskoi konferentsii po molniezashchite [Proceedings of the IV Russian Conference on Lightning Protection]. NPO «Strimer», Sankt-Peterburg, 2014, pp. 1-16. (Rus).

6. Chernukhin A.Iu. Parameters of pulse corona on metal roads in strength electric field. Bulletin of NTU «KhPІ», 2014, no.50, pp. 155-160. (Rus).

7. Chernukhin A.Iu., Kniazev V.V. A features of streamer crown are from cored air terminals. Bulletin of NTU «KhPІ», 2015, no.20, pp. 149-155. (Rus).

8. Kniazev V.V., Chernukhin A.Iu. Effects of corona in pre-discharge conditions. Trudy IV Rossiiskoi konferentsii po molniezashchite [Proceedings of the IV Russian Conference on Lightning Protection]. NPO «Strimer», Sankt-Peterburg, 2014, pp.62-70. (Rus).

9. Rezinkina M.M. Simulation of electric fields in the presence of rods with rounded upper ends. Technical Physics, 2015, vol.60, no.3, pp. 337-343. doi: 10.1134/S1063784215030238.

10. Vernon Cooray. Lightning Protection. Ins.Eng.Tech., London, UK, 2010. 1070 р.

Published

2017-06-29

How to Cite

Chernukhin, A. Y. (2017). INFLUENCE OF CORONARY DISCHARGE PARAMETERS ON THE EFFICIENCY OF LIGHTNING PROTECTION SYSTEM ELEMENTS. Electrical Engineering & Electromechanics, (3), 47–56. https://doi.org/10.20998/2074-272X.2017.3.07

Issue

Section

Engineering Electrophysics. High Electric and Magnetic Field Engineering