ESTIMATION CRITERIA FOR DEGREE OF PAPER-IMPREGNATED INSULATED POWER CABLE AGEING

Authors

  • G. V. Bezprozvannych National Technical University "Kharkiv Polytechnic Institute", Ukraine
  • E. S. Moskvitin National Technical University "Kharkiv Polytechnic Institute", Ukraine

DOI:

https://doi.org/10.20998/2074-272X.2013.4.05

Keywords:

power cables, paper-impregnated insulation, mechanical and thermal ageing, double bends number, dielectric loss tangent, linear and exponential regression analysis

Abstract

Correlation between parameters characterizing mechanical and thermal ageing of paper-impregnated insulation of medium voltage power cables is revealed. On the basis of linear and exponential regression analysis at confidence coefficient of 0.95, critical values of dielectric loss tangent of wrapping and phase insulation corresponding to the cable life termination are found.

References

Diagnostika i monitoring kabel'nyh setej srednih klassov napryazheniya / K.P. Kadomskaya, V.E. Kachesov, Yu.A. Lavrov i dr. // `Elektrotehnika. − 2000. − № 11. - S. 48-51.

Kudrin B.I. Rangovyj analiz tehnocenoza "Kabel'naya set' 3-10 kV OAO "Zapadno-Sibirskij metallurgicheskij kombinat" / B.I. Kudrin, G.M. Lebedev, A.Yu. Gaponenko // Promyshlennaya `energetika. - 2007. - № 3. - S. 5-12.

Privalov I.N. Nerazrushayuschaya diagnostika silovyh kabel'nyh linij nominal'nym napryazheniem 6-35 kV // `Elektrotehnicheskij rynok. - 2008. - № 2.

Kustov A. Suschestvuet li v Rossii diagnostika silovyh kabel'nyh linij i `elektrooborudovaniya… i zachem ona nuzhna? / `Energetika i promyshlennost' Rossii. - 2006. - № 8 (72).

Moskvitin E.S. Slozhnost' primeneniya nerazrushayuschih metodov ispytaniya bumazhno-maslyanoj izolyacii kabelej pri diagnostike ih sostoyaniya / E.S. Moskvitin. // Informacionnye tehnologii: nauka, tehnika, tehnologiya, obrazovanie, zdorov'e: Materialy XVII Mezhdunarodnoj nauchno-prakticheskoj konferencii 22-22 maya 2009. Har'kov: Chast' I. - S. 542.

Moskvitin E.S. Ocenka tehnicheskogo sostoyaniya vysokovol'tnyh kabelej s bumazhno-maslyanoj izolyaciej po chislu dvojnyh peregibov / E.S. Moskvitin // Vestnik NTU "HPI". - №3 4. - 2006. - S. 34-40.

Besprozvannyh A.V. Chislo dvojnyh peregibov kak indikator stepeni stareniya kabel'nyh bumag / A.V. Besprozvannyh, E.S. Moskvitin. − Elektrotehnіka і elektromehanіka. − 2011. − № 3. − S. 62-66.

Besprozvannyh A.V. / Obsledovanie izolyacii trehfaznyh kabelej v metallicheskoj obolochke // A.V. Besprozvannyh, B.G. Naboka, E.S. Moskvitin // `Elektrichestvo. - №1. - 2010. - S. 48-54.

Naboka B.G. Kriterii po tangensu ugla di`elektricheskih poter' dlya ocenki tehnicheskogo sostoyaniya silovyh kabelej s bumazhno-propitannoj izolyaciej v `ekspluatacii / B.G. Naboka, A.V. Besprozvannyh, E.S. Moskvitin i dr. // Vestnik NTU "HPI". - 2010. - №5. - S. 76-83.

Naboka B.G. Diagnostika kabel'nyh linij `energosistem po tangensu ugla di`elektricheskih poter' i postoyannoj vremeni samorazryada bumazhno-propitannoj izolyaciej / B.G. Naboka, A.V. Besprozvannyh, E.S. Moskvitin i dr. // Elektrotehnіka і elektromehanіka. - 2011. - № 2. - S. 65-69.

Moskvitin E.S. Kontrol' processov stareniya silovyh kabelej s bumazhno-propitannoj izolyaciej po izmeneniyu di`elektricheskih harakteristik izolyacionnyh promezhutkov / E.S. Moskvitin // Vestnik NTU "HPI". -2011. - № 3. - S. 95-106.

Published

2013-09-07

How to Cite

Bezprozvannych, G. V., & Moskvitin, E. S. (2013). ESTIMATION CRITERIA FOR DEGREE OF PAPER-IMPREGNATED INSULATED POWER CABLE AGEING. Electrical Engineering & Electromechanics, (4), 32–36. https://doi.org/10.20998/2074-272X.2013.4.05

Issue

Section

Engineering Electrophysics. High Electric and Magnetic Field Engineering